PEA-M100/125/140GAA 10-14 kW ducted air conditioning

  • PEA-M100GAA ducted air conditioning for offices
  • Flexible duct design

    A flexible duct design and 150Pa external static high-pressure are incorporated. The increased variation in airflow options ensures operation that best matches virtually all room layouts.

    Flexible duct design

Freedom in installation

Versatile and easy installation is possible, for example, it is possible to adjust the distance between the air intake and the air outlet vents to create the optimal airflow configuration.

Flexible duct design

A flexible duct design and 150Pa external static high-pressure are incorporated. The increased variation in airflow options ensures operation that best matches virtually all room layouts.

Quiet operation

We recognise that noise affects comfort, so we constantly work to make our air conditioners as quiet as possible. With improvements to our fan blades combined with our grille shape to our outdoor unit, itís even quieter when in low noise mode. We want you to feel it, not hear it.

Uninterrupted design

Mitsubishi Electric ducted systems allow for a range of diffuser designs to best suit your home decor. Talk to your installer about what is right for you.

Pecise control

We recognise that noise affects comfort, so we constantly work to make our air conditioners as quiet as possible. With improvements to our fan blades combined with our grille shape to our outdoor unit, itís even quieter when in low noise mode. We want you to feel it, not hear it.

5 year parts and labour warranty

Mitsubishi Electric air conditioners used in residential applications are covered by a full 5 year parts and labour warranty. Delivering optimum performance year in year out. Read terms & conditions.

The products of Mitsubishi Electric Australia come with guarantees, additional to this Warranty that cannot be excluded under the Australian Consumer Law.
You are entitled to a replacement or refund for a major failure and for compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and failure does not amount to a major failure.

Longer maximum piping length

It is now possible to pipe refrigerant up to 75 metres to the concealed ceiling unit, therefore creating a wide range of layout possibilities for unit installation.

Wi-Fi Control

This innovative technology connects your domestic Mitsubishi Electric air conditioners to your smartphone, tablet or online account, giving you the freedom to fully control each unit on-the-go via an Internet connection. Optional additional adapter MAC-568IF-E required per unit.

PAR-CT01MAA MA Touch Remote Controller

The full colour touch controller PAR-CT01MAA enables the control of both residential and commercial air conditioning applications. It has a customisable 3.5 inch colour LCD touch panel that makes it easy to use. Available in white or premium black finishes, suitable for any décor.

PAR-40MAA Wall mounted controller

This attractive full dot liquid crystal display incorporates a large backlit screen and simple menus for easy operation. You can set up to 8 temperature and airflow patterns per day for seven days. Perfect for the busy home and office or retail store.

Zone Control

Control 4 or 8 zones with the Mitsubishi Electric Zone Controller. The optional Zone Controller features three built-in sensors (temperature, brightness & occupancy), and allows monitoring and scheduled operation of the air conditioning unit and zones. These features combine to provide a comfortable air environment and greater control over energy consumption and costs.

Model Name PEA-M100GAA  PEA-M125GAA PEA-M140GAA
Indoor Unit PEA-M100GAA PEA-M125GAA PEA-M140GAA
Outdoor Unit - Single Phase PUZ-ZM100VKA PUZ-ZM125VKA PUZ-ZM140VKA
Refrigerant R32
 
Power Supply
Source Outdoor power supply
Outdoor 230V, Single-phase, 50 Hz
Indoor -
 
Cooling
Capacity (Min - Rated - Max) kW 4.9 - 10.0 - 11.14 5.5 - 12.5 - 14.0 6.2 - 14.0 - 15.3
Total Input (Rated) kW 2.39 3.52 4.10
AEER/EER 4.01 / 4.18 3.45 / 3.55 3.33 / 3.41
AEER (Part-load %) *1   - - -
Air Volume (In) (Lo-Hi) L/s 567-700 800-1000 800-1000
 
Heating
Capacity (Min - Rated - Max) kW 4.5 - 11.2 - 14.0 5.0 - 14.0 - 16.0 5.7 - 16.0 - 18.0
Total Input (Rated) kW 2.51 3.27 3.90
ACOP/COP*3 kW 4.28 / 4.46 4.15 / 4.28 3.99 / 4.10
ACOP (Part-load %) *1   - - -
Air Volume (In) (Lo-Hi) 567-700 800-1000 800-1000
       
Indoor Unit      
Input (Rated) kW 0.21 0.49 0.49
Dimensions (HxWxD) mm 400 x 1400 x 634
Weight kg 63
Static Pressure   50/100/150
       
Outdoor Unit      
Dimensions (HxWxD) mm 1338 x 1050 x 330
Weight kg 113 113 113
Breaker Size A 32 32 40
       
Ext. Piping      
Diameter (Gas/Liquid) mm 15.88 / 9.52
Max. Length/Height m 75 / 30
       
Guaranteed Operating Range        
Cooling *2 °C -5 (-15) ~ 452
Heating °C -20 ~ 21

*1 MEPS compliant at part load.

*2 With the optional air protection guide, the operation at -15°C outdoor temperature is possible.

 

(Rating Conditions)
Cooling:

Indoor 27°C, D.B./19°C, W.B.

Outdoor 35°C, D.B./24°C, W.B.

Heating:

Indoor 20°C, D.B./15°C, W.B.

Outdoor 7°C, D.B./6°C, W.B.

 

Model Name PEA-M100GAA  PEA-M125GAA PEA-M140GAA
Indoor Unit PEA-M100GAA PEA-M125GAA PEA-M140GAA
Outdoor Unit - Three Phase PUZ-ZM100YKA PUZ-ZM125YKA PUZ-ZM140YKA
Refrigerant R32
 
Power Supply
Source Outdoor power supply
Outdoor 400V, Three-phase, 50 Hz
Indoor -
 
Cooling
Capacity (Min - Rated - Max) kW 4.9 - 10.0 - 11.14 5.5 - 12.5 - 14.0 6.2 - 14.0 - 15.3
Total Input (Rated) kW 2.39 3.52 4.10
AEER/EER 3.26 / 3.43 3.40 / 3.55 3.29 / 3.41
AEER (Part-load %) *1   - - -
Air Volume (In) (Lo-Hi) L/s 567-700 800-1000 800-1000
 
Heating
Capacity (Min - Rated - Max) kW 4.5 - 11.2 - 14.0 5.0 - 14.0 - 16.0 5.7 - 16.0 - 18.0
Total Input (Rated) kW 2.51 3.27 3.90
ACOP/COP*3 kW 3.55 / 3.73 4.09 / 4.28 3.95 / 4.10
ACOP (Part-load %) *1   - - -
Air Volume (In) (Lo-Hi) 567-700 800-1000 800-1000
       
Indoor Unit      
Input (Rated) kW 0.21 0.49 0.49
Dimensions (HxWxD) mm 400 x 1400 x 634
Weight kg 63
Static Pressure   50/100/150
       
Outdoor Unit      
Dimensions (HxWxD) mm 1338 x 1050 x 330
Weight kg 114 114 114
Breaker Size A 16 16 16
       
Ext. Piping      
Diameter (Gas/Liquid) mm 15.88 / 9.52
Max. Length/Height m 75 / 30
       
Guaranteed Operating Range        
Cooling *2 °C -5 (-15) ~ 452
Heating °C -20 ~ 21

*1 MEPS compliant at part load.

*2 With the optional air protection guide, the operation at -15°C outdoor temperature is possible.

 

(Rating Conditions)
Cooling:

Indoor 27°C, D.B./19°C, W.B.

Outdoor 35°C, D.B./24°C, W.B.

Heating:

Indoor 20°C, D.B./15°C, W.B.

Outdoor 7°C, D.B./6°C, W.B.

 